Bathroom Exhaust Fan Size Calculator

Up to 100 square feet, a bathroom fan needs 1 CFM per square foot of floor and never less than 50 CFM. A bigger bathroom is sized by its fixtures: 50 CFM each for the toilet, shower and tub, 100 for a jetted tub. Then buy a little above that, because the duct takes its share.

Size your bathroom fan

The room and its fixtures give the airflow the fan must move, the rating to buy and the most noise to accept, and a check that the duct can carry it.

Feet with decimals: 7 ft 6 in is 7.5. The floor of the whole bathroom, wall to wall.

Fixtures (they set the size over 100 sq ft)
The fan will run

The duct

From the spec sheet, the airflow at 0.25 in. of static pressure. Blank checks the rating to buy.

The fan must move at least 0 CFM
Floor area
Sized by
Buy a fan rated at least
Loudest to accept

    How big a fan

    These are the rates the Home Ventilating Institute (HVI) recommends for a fan you switch on when the room is used:

    BathroomFan size
    Up to 100 sq ft1 CFM per square foot of floor, at least 50 CFM
    Over 100 sq ftAdd up the fixtures: toilet 50, shower 50, bathtub 50, jetted tub 100 CFM
    Fan running all the time20 CFM, in place of a 50 CFM switched fan

    So a 5 by 8 ft hall bath, 40 sq ft, needs the 50 CFM minimum; an 8 by 10 ft bath needs 80; and a 12 by 12 ft primary bath with a toilet, a shower and a tub needs 150. HomeAdvisor's sizing table agrees: 50 to 60 CFM for a 40 sq ft bath, 150 to 250 for a 144 sq ft one. HVI also says an enclosed toilet should have its own fan, and that a fan rated for wet areas should go over the shower or tub where possible.

    The code minimums are lower. The Department of Energy's Building America Solution Center gives the International Residential Code's and ASHRAE 62.2's figures as at least 50 CFM for a switched fan or 20 CFM for one that runs continuously. HVI's rates are what keep a bigger room clear.

    What to buy

    The rating on the box is measured in a lab, and once the fan is ducted it moves less. The Building America guide says ENERGY STAR recommends a fan rated at least 70 CFM to deliver the 50 CFM a switched fan needs, and one rated over 50 CFM to deliver a continuous 20. The calculator uses 70 as the floor for any switched fan whose need is under 70; that extension to needs between 50 and 70 is our reading. Above 70 it gives the need itself, and the duct check below tells you whether your duct can deliver it.

    For noise, the same guide says ASHRAE 62.2 requires 3 sones or less for a fan you switch on and 1 sone or less for one that runs all the time, and that ENERGY STAR recommends the same limits. A quieter fan gets used. HVI recommends a timer or control that keeps the fan running 20 minutes after each use, and a 3/4-inch gap under the door so replacement air can get in. Is a humidity sensing fan worth it? looks at the automatic option.

    Is the duct short and wide enough?

    Most weak bathroom fans are a duct problem. The building code limits how long an exhaust duct can be for the fan it serves, in Table M1504.2 of the International Residential Code (as UpCodes publishes it). The table assumes no elbows; take 15 ft off the allowance for each one.

    Duct50 CFM fan80 CFM100 CFM125 CFM150 CFM
    3 in smooth5 ftNot allowedNot allowedNot allowedNot allowed
    4 in flexible56 ft4 ftNot allowedNot allowedNot allowed
    4 in smooth114 ft31 ft10 ftNot allowedNot allowed
    5 in flexibleNo limit81 ft42 ft16 ft2 ft
    5 in smoothNo limit152 ft91 ft51 ft28 ft
    6 in flexibleNo limitNo limit158 ft91 ft55 ft
    6 in smoothNo limitNo limitNo limit168 ft112 ft

    The fan's rating in the table is its airflow at 0.25 inches of static pressure, which a good spec sheet lists alongside the usual figure. A 3-inch flexible duct is not allowed at any size, and the 4-inch flexible duct so many fans are hung on carries an 80 CFM fan only 4 ft: one elbow uses that up. That is the commonest reason a new fan still leaves the mirror fogged. The calculator reads a fan between two columns in the next one up, and the code also accepts a duct that meets the fan maker's design criteria, or one whose airflow is measured once installed.

    The Building America guide adds the rest: duct to the outside, never into the attic, crawlspace or a wall; use smooth duct where you can and pull flex tight; keep the first two to three feet straight before any elbow; prefer gradual bends to sharp ones; insulate the duct against condensation; and end it at a cap with a damper, at least 3 ft from a gravity air inlet and 10 ft from a mechanical one (IRC M1504.3).

    From a number to a quote

    With a CFM and a sone limit you have what an installer asks for. What size bathroom exhaust fan you need walks through measuring, what a bathroom fan replacement costs prices the job, and the quote checker puts a bid against the published figures. Who to call is in electrician or handyman for a bathroom fan, whether you need a permit in permits for replacing a bathroom exhaust fan, and when it is time in signs your bathroom fan needs replacing.